CoEpower Active Power Filter (APF) helps to solve LED Source Harmonics Filtration

1. نظرة عامة على المشروع

This supermarket was built many years ago, and harmonic problems were not considered in the power system configuration then. When designing the power distribution system, كان قطر كابل الطور N أصغر من كابل A/B/C ثلاثي الطور.

The building is divided into three floors. The first floor is a supermarket, and the second and third floors are clothing stores. In the first floor’s power distribution circuit, serious N-phase heating, and excessive current problems occurred.

2. مخطط نظام التوزيع والأحمال التوافقية الرئيسية

There are 4 load outlet cabinets in the power distribution room, among which the power consumption of the supermarket on the first floor is led out from the 3# و 4# feeder cabinets.

In the power distribution structure, the power upstream of the 3# و 4# feeder cabinets is a dual power switch, and this switch is a 4P switch.

The typical harmonic source at this site is an LED indicator light

The first symptom of the problem discovered at the site was the heating problem of the N-phase shell of the dual power switch.

3. Harmonic data testing and analysis

After selecting the on-site transformer, we conducted a test at the incoming cabinet location to gain an overall understanding of the on-site power quality issues.

4. Harmonic solution

On-site improvement needs include resolving the overheating of the N-phase cables and switches in the first-floor supermarket. As the main harmonic source equipment is located in the first-floor supermarket, targeted measures are chosen to address the harmonic issues in the 3# و 4# feeder cabinets to reduce the N-phase current at the dual power switch positions and resolve the overheating issue in this N-phase location.

Equipment Selection: فلتر الطاقة النشط (APF)

Equipment model: CoEpo APF/200-0.4-D

Management method: local treatment

Installation capacity: 200أ

Installation method: rack type

موقع التثبيت: power distribution room

5. تأثير

After harmonic improvement by active power filter:

1. The system’s current waveform has been significantly improved, from the original distorted waveform to a normal sine wave waveform;

2. The N-phase current dropped from the 251.4A to 17.2A. The N-phase current dropped significantly, so the N-phase cable heating problem is solved;

3. The system’s total harmonic distortion rate dropped from 47.2% ل 4.6%, and the harmonic control effect was significant.

العلامات: Power system configuration, Harmonic solution, فلتر الطاقة النشط (APF), CoEpo APF/200-0.4-D, 200A APF, rack type Active Power Filter, الموردين, الشركات المصنعة, مصنع, بالجملة, يشتري, سعر, اقتباس, حجم كبير, للبيع, شركات, مخزون, يكلف.