Coepo 300a Power Power Filter APF APF برای بیمارستان

پیش زمینه پروژه

The hospital’s equipment was tested, و تجزیه و تحلیل داده های آزمون نشان داد که THDI تولید شده توسط شتاب دهنده ها, دستگاه های اشعه ایکس, and gastrointestinal machines was approximately 50 %—60 %; CT (توموگرافی کامپیوتری), MRI, and DSA (digital subtraction angiography) were approximately 30%; electronic testing equipment and operating rooms were between 10% وت 15%; and frequency conversion equipment was approximately 35%.

راه حل هارمونیک

300یک فیلتر قدرت فعال APF

Two transformers are on site, each of which needs to be equipped with a 150A فیلتر برق فعال device.

انتخاب تجهیزات: فیلتر برق فعال (APF)

مدل تجهیزات: CoEpo APF/150-0.4-D*2

Governance method: درمان موضعی

ظرفیت نصب: 300بوها

روش نصب: نوع قفسه

محل نصب: Power distribution room

اثر

Two 150A active power filters can effectively control the 3rd, 5th, 7th, and 11th order current harmonics.

Active power filters have a fast response speed, full compensation response speed ≤10ms, harmonic compensation capacity of 2~50 times, and flexible configuration. According to the actual power quality status of the system, the control priority can be set to maximize the module utilization.

برچسب ها: فیلتر برق فعال, APF, CoEpo APF/150-0.4-D*2, 300یک APF, 150A active power filters, فیلتر قدرت فعال از نوع قفسه, تهیه کننده, تولید کنندگان, کارخانه, عمده, خرید کردن, قیمت, نقل قول, انبوه, برای فروش, شرکت, انبار, هزینه.