پیش زمینه پروژه:
در طی فرآیند تولید و توسعه, یک سازنده از اینورتر با قدرت بالا برای اشکال زدایی استفاده کرد. در حین عملکرد اینورتر, very serious harmonic distortion occurred. The equipment operating current was about 1200A, and the on-site harmonic current distortion rate reached 30%.
In December 2019, our company’s active power filter was installed to treat the test bench for harmonics. The initial equipment installation capacity was 300A. After filtering, the system harmonic current distortion rate dropped from the original 30% به 11%.

راه حل هارمونیک:
To achieve better power quality effects, it was decided to expand the capacity of the active power filter equipment, and finally, the original active power filter equipment was increased to 750A. After the capacity increase, the system harmonic current distortion rate dropped to 4.8%.
انتخاب تجهیزات: فیلتر برق فعال (APF)
مدل تجهیزات: CoEpo APF/750- 0.4-د
Governance method: درمان موضعی
ظرفیت نصب:750بوها
روش نصب: Rack Mounted
اثر:
Our active power filter (APF), the harmonic current distortion rate generated by the inverter in the system, has been significantly improved. The total harmonic distortion rate of the system has dropped from 36% به 4.3%, and the main harmonic distortion problems of 5/7/11/13 times have been significantly improved.