The hospital’s equipment was tested, и анализ тестовых данных показал, что THDI, сгенерированная акселераторами, Рентгеновские машины, and gastrointestinal machines was approximately 50 %—60 %; КТ (Компьютерная томография), MRI, and DSA (digital subtraction angiography) were approximately 30%; electronic testing equipment and operating rooms were between 10% и 15%; and frequency conversion equipment was approximately 35%.
Гармоническое решение

Two transformers are on site, each of which needs to be equipped with a 150A Активная мощность фильтра device.
Выбор оборудования: Активная мощность фильтра (APF)
Модель оборудования: CoEpo APF/150-0.4-D*2
Метод управления: местное лечение
Установка: 300А
Метод установки: тип стойки
Место установки: Распределение энергии
Эффект
Two 150A active power filters can effectively control the 3rd, 5тур, 7тур, and 11th order current harmonics.
Active power filters have a fast response speed, full compensation response speed ≤10ms, harmonic compensation capacity of 2~50 times, and flexible configuration. According to the actual power quality status of the system, the control priority can be set to maximize the module utilization.