Пример использования активного фильтра гармоник CoEpower: Снижение гармоник на заводе карбида кальция

В современных промышленных энергосистемах, широкое применение частотно-регулируемых приводов (VFDS), инверторное оборудование, and nonlinear loads has significantly improved production efficiency and energy savings. Однако, these technologies also introduce severe harmonic distortion into electrical distribution systems.

Industries such as chemical processing, металлургия, mining, and calcium carbide production rely heavily on high-power electrical equipment and inverter-controlled systems. Without proper harmonic control, excessive harmonics can threaten transformer safety, destabilize power systems, увеличить потери энергии, and shorten equipment lifespan.

As a Senior Electrical Engineer at CoEpower, I will share a successful harmonic mitigation project implemented at Xinjiang Zhongtai Chemical Shengxiong Calcium Carbide Plant. This case study demonstrates how CoEpower’s intelligent Active Harmonic Filter (AHF) technology effectively reduced total harmonic distortion from approximately 35% ниже 6%, greatly improving power quality and operational stability.

Предыстория проекта

The Xinjiang Zhongtai Chemical Shengxiong Calcium Carbide Plant project includes a large number of high-power water pump systems combined with multiple frequency converters used for pump regulation and process control.

While inverter technology improves operational flexibility and energy efficiency, the massive use of frequency converters generated severe harmonic pollution throughout the plant’s 0.4kV low-voltage distribution system.

The excessive harmonic currents caused several major issues:

  • Serious current waveform distortion
  • Transformer overheating risks
  • Increased system losses
  • Reduced electrical efficiency
  • Potential equipment malfunction
  • Electrical safety concerns
  • Instability in the power distribution network

To ensure long-term safe and reliable operation, the plant urgently required a professional harmonic compensation solution.

Electrical System Overview

400A Active Harmonic Filters - Коэффициент

The project focused on the 0.4kV low-voltage power distribution system of the Phase II Water and Gas Section.

Installation Information

Место установки: Phase II Water and Gas Section I & II Distribution Cabinets

Установленное оборудование: WK-400-APF44L/R Intelligent Активные гармонические фильтры

Number of Units: 2 Sets

Total Installed Capacity: 400А

The APF systems were installed directly into the low-voltage distribution cabinets to provide centralized harmonic compensation for the downstream nonlinear loads.

Harmonic Problems Before Compensation

Before the Active Harmonic Filters were activated, severe harmonic distortion was observed throughout the electrical system.

Typical Harmonic Characteristics

The measured current waveform displayed a classic double-headed waveform pattern, which is a typical indication of dominant 5th harmonic distortion generated by frequency converters.

The major harmonic orders identified included:

  • 5гармоника
  • 7гармоника
  • 11гармоника
  • 13гармоника

These harmonics are common in industrial inverter systems using rectifier circuits and nonlinear loads.

Трансформатор #1 Harmonic Compensation Results

After the CoEpower Active Harmonic Filter system was activated, the electrical performance improved dramatically.

Current Waveform Improvement

The distorted current waveform returned to a near-sinusoidal shape after compensation.

Due to the elimination of harmonic currents:

  • Apparent current decreased
  • System efficiency improved
  • Transformer loading conditions improved

The three-phase RMS current values reduced from approximately 800A to around 780A.

THDi Reduction Performance

Before Compensation

THDi ≈ 35%

After Compensation

THDi ≈ 5.9%

This represents a major improvement in overall power quality.

Harmonic Current Reduction

The compensation performance for major harmonic orders was highly effective.

5th Harmonic Current

Reduced from 248.2A to 6.5A

7th Harmonic Current

Reduced from 77.6A to 3.1A

11th Harmonic Current

Reduced from 58.3A to 6.9A

The APF system successfully suppressed the dominant low-order harmonics responsible for the system distortion.

Трансформатор #2 Harmonic Compensation Results

After commissioning the CoEpower intelligent Active Harmonic Filter system, the electrical conditions improved substantially.

Current Waveform Restoration

The APF system effectively filtered the distorted current waveform, restoring it to a sinusoidal condition.

As harmonic currents were eliminated:

  • Apparent current decreased
  • Transformer operating conditions improved
  • Electrical losses were reduced

The RMS current values decreased from approximately 1100A to about 1000A.

THDi Reduction Results

Before Compensation

THDi ≈ 33%

After Compensation

THDi ≈ 6%

The power quality improvement fully met the project requirements.

Harmonic Suppression Performance

5th Harmonic Current

Reduced from 308.7A to 45.4A

7th Harmonic Current

Reduced from 93.5A to 15A

The 11th and 13th harmonic currents were also significantly reduced.

These results clearly demonstrate the effectiveness of CoEpower’s intelligent harmonic compensation technology.

Project Summary

Following the installation of CoEpower intelligent Active Harmonic Compensation equipment, the harmonic distortion problem in the 0.4kV low-voltage distribution system of Xinjiang Zhongtai Chemical Shengxiong Calcium Carbide Plant was significantly improved.

The project achieved:

  • THDi reduction from approximately 35% ниже 6%
  • Significant suppression of 5th, 7тур, 11тур, and 13th harmonics
  • Improved transformer operating conditions
  • Reduced apparent current
  • Enhanced electrical system safety
  • Increased power system stability

The successful operation of this project further demonstrates the effectiveness and reliability of CoEpower Active Harmonic Filter solutions in heavy industrial applications.

Заключение

As industrial facilities continue adopting inverter-driven equipment and automated systems, harmonic distortion is becoming an increasingly important power quality challenge.

This successful case study at Xinjiang Zhongtai Chemical Shengxiong Calcium Carbide Plant highlights how CoEpower intelligent Active Harmonic Filters can effectively solve severe harmonic problems and improve the long-term reliability of industrial electrical systems.

By reducing harmonic distortion from 35% ниже 6%, the project significantly enhanced transformer safety, optimized power quality, and improved operational stability.

If your facility is experiencing harmonic distortion, excessive THDi, or power quality issues caused by nonlinear loads, CoEpower can provide customized harmonic analysis and advanced harmonic mitigation solutions tailored to your application.

For more information about industrial harmonic compensation systems, visit CoEpower Official Website: https://www.coepowers.com/

Keyword Tags: Активный гармонический фильтр, Гармоническое смягчение, harmonic compensation, Снижение THDi, Активная мощность фильтра, VFD harmonic solution, Промышленное качество электроэнергии, harmonic debugging case study, calcium carbide plant electrical system, снижение гармонических искажений, Гармонический фильтр низкого напряжения, 0.4kV harmonic compensation, inverter harmonic suppression, CoEpower НПФ, transformer harmonic protection, industrial harmonic filter solution, поставщики, производители, фабрика, компания, Китай, оптом, купить, цена, цитата, масса, для продажи, Компании, запас, расходы.

Связанный продукт

Похожие блоги

Получите предложение сегодня

Связанные посты

Пример проекта компенсации гармоник для мощных преобразователей частоты на химическом заводе - Коэффициент

Пример гармонической компенсации: Уменьшение THDi от 35.8% к 5% с активными фильтрами гармоник CoEpower для мощных преобразователей частоты на химическом заводе

Поскольку современные промышленные предприятия все чаще применяют приводы с регулируемой частотой (VFDS) и системы двигателей с инверторным управлением, гармонические искажения стали одним из

Читать далее
Как технология SVG решила проблемы с реактивной мощностью

Пример проекта сварки ферм в Синьцзяне: Как технология SVG решила проблемы с реактивной мощностью и снизила затраты на электроэнергию

Введение: Инженерный взгляд на качество промышленной электроэнергии. Старший инженер-электрик в CoEpower Electric., Я работал во многих промышленных

Читать далее
Обновите предпочтения файлов cookie

Попросите быструю цитату

Мы свяжемся с вами внутри 1 рабочий день.