ในระบบไฟฟ้าอุตสาหกรรมสมัยใหม่, การใช้ไดรฟ์ความถี่แบบแปรผันอย่างแพร่หลาย (VFDS), อุปกรณ์อินเวอร์เตอร์, and nonlinear loads has significantly improved production efficiency and energy savings. อย่างไรก็ตาม, these technologies also introduce severe harmonic distortion into electrical distribution systems.
Industries such as chemical processing, โลหะวิทยา, mining, and calcium carbide production rely heavily on high-power electrical equipment and inverter-controlled systems. Without proper harmonic control, excessive harmonics can threaten transformer safety, destabilize power systems, เพิ่มการสูญเสียพลังงาน, and shorten equipment lifespan.
As a Senior Electrical Engineer at CoEpower, I will share a successful harmonic mitigation project implemented at Xinjiang Zhongtai Chemical Shengxiong Calcium Carbide Plant. This case study demonstrates how CoEpower’s intelligent Active Harmonic Filter (อ่า) technology effectively reduced total harmonic distortion from approximately 35% ไปด้านล่าง 6%, greatly improving power quality and operational stability.
ความเป็นมาของโครงการ
The Xinjiang Zhongtai Chemical Shengxiong Calcium Carbide Plant project includes a large number of high-power water pump systems combined with multiple frequency converters used for pump regulation and process control.
While inverter technology improves operational flexibility and energy efficiency, the massive use of frequency converters generated severe harmonic pollution throughout the plant’s 0.4kV low-voltage distribution system.
The excessive harmonic currents caused several major issues:
- Serious current waveform distortion
- Transformer overheating risks
- Increased system losses
- Reduced electrical efficiency
- Potential equipment malfunction
- Electrical safety concerns
- Instability in the power distribution network
To ensure long-term safe and reliable operation, the plant urgently required a professional harmonic compensation solution.
Electrical System Overview

The project focused on the 0.4kV low-voltage power distribution system of the Phase II Water and Gas Section.
Installation Information
สถานที่ติดตั้ง: Phase II Water and Gas Section I & II Distribution Cabinets
อุปกรณ์ที่ติดตั้ง: WK-400-APF44L/R Intelligent ตัวกรองฮาร์มอนิกที่ใช้งานอยู่
Number of Units: 2 Sets
Total Installed Capacity: 400อัน
The APF systems were installed directly into the low-voltage distribution cabinets to provide centralized harmonic compensation for the downstream nonlinear loads.
Harmonic Problems Before Compensation
Before the Active Harmonic Filters were activated, severe harmonic distortion was observed throughout the electrical system.
Typical Harmonic Characteristics
The measured current waveform displayed a classic double-headed waveform pattern, which is a typical indication of dominant 5th harmonic distortion generated by frequency converters.
The major harmonic orders identified included:
- 5ฮาร์มอนิก
- 7ฮาร์มอนิก
- 11ฮาร์มอนิก
- 13ฮาร์มอนิก
These harmonics are common in industrial inverter systems using rectifier circuits and nonlinear loads.
หม้อแปลงไฟฟ้า #1 Harmonic Compensation Results
After the CoEpower Active Harmonic Filter system was activated, the electrical performance improved dramatically.
Current Waveform Improvement
The distorted current waveform returned to a near-sinusoidal shape after compensation.
Due to the elimination of harmonic currents:
- Apparent current decreased
- System efficiency improved
- Transformer loading conditions improved
The three-phase RMS current values reduced from approximately 800A to around 780A.
THDi Reduction Performance
Before Compensation
THDi ≈ 35%
After Compensation
THDi ≈ 5.9%
This represents a major improvement in overall power quality.
Harmonic Current Reduction
The compensation performance for major harmonic orders was highly effective.
5th Harmonic Current
Reduced from 248.2A to 6.5A
7th Harmonic Current
Reduced from 77.6A to 3.1A
11th Harmonic Current
Reduced from 58.3A to 6.9A
The APF system successfully suppressed the dominant low-order harmonics responsible for the system distortion.
หม้อแปลงไฟฟ้า #2 Harmonic Compensation Results
After commissioning the CoEpower intelligent Active Harmonic Filter system, the electrical conditions improved substantially.
Current Waveform Restoration
The APF system effectively filtered the distorted current waveform, restoring it to a sinusoidal condition.
As harmonic currents were eliminated:
- Apparent current decreased
- Transformer operating conditions improved
- Electrical losses were reduced
The RMS current values decreased from approximately 1100A to about 1000A.
THDi Reduction Results
Before Compensation
THDi ≈ 33%
After Compensation
THDi ≈ 6%
The power quality improvement fully met the project requirements.
Harmonic Suppression Performance
5th Harmonic Current
Reduced from 308.7A to 45.4A
7th Harmonic Current
Reduced from 93.5A to 15A
The 11th and 13th harmonic currents were also significantly reduced.
These results clearly demonstrate the effectiveness of CoEpower’s intelligent harmonic compensation technology.
Project Summary
Following the installation of CoEpower intelligent Active Harmonic Compensation equipment, the harmonic distortion problem in the 0.4kV low-voltage distribution system of Xinjiang Zhongtai Chemical Shengxiong Calcium Carbide Plant was significantly improved.
The project achieved:
- THDi reduction from approximately 35% ไปด้านล่าง 6%
- Significant suppression of 5th, 7ไทย, 11ไทย, and 13th harmonics
- Improved transformer operating conditions
- Reduced apparent current
- Enhanced electrical system safety
- Increased power system stability
The successful operation of this project further demonstrates the effectiveness and reliability of CoEpower Active Harmonic Filter solutions in heavy industrial applications.
บทสรุป
As industrial facilities continue adopting inverter-driven equipment and automated systems, harmonic distortion is becoming an increasingly important power quality challenge.
This successful case study at Xinjiang Zhongtai Chemical Shengxiong Calcium Carbide Plant highlights how CoEpower intelligent Active Harmonic Filters can effectively solve severe harmonic problems and improve the long-term reliability of industrial electrical systems.
By reducing harmonic distortion from 35% ไปด้านล่าง 6%, the project significantly enhanced transformer safety, optimized power quality, and improved operational stability.
If your facility is experiencing harmonic distortion, excessive THDi, or power quality issues caused by nonlinear loads, CoEpower can provide customized harmonic analysis and advanced harmonic mitigation solutions tailored to your application.
For more information about industrial harmonic compensation systems, visit CoEpower Official Website: https://www.coepowers.com/
Keyword Tags: ตัวกรองฮาร์มอนิกที่ใช้งานอยู่, การบรรเทาฮาร์มอนิก, harmonic compensation, การลด THDi, ตัวกรองพลังงานที่ใช้งานอยู่, VFD harmonic solution, คุณภาพพลังงานอุตสาหกรรม, harmonic debugging case study, calcium carbide plant electrical system, การลดความผิดเพี้ยนของฮาร์มอนิก, ตัวกรองฮาร์มอนิกแรงดันต่ำ, 0.4kV harmonic compensation, inverter harmonic suppression, โคอีพาวเวอร์ เอพีเอฟ, transformer harmonic protection, industrial harmonic filter solution, ซัพพลายเออร์, ผู้ผลิต, โรงงาน, บริษัท, จีน, ขายส่ง, ซื้อ, ราคา, ใบเสนอราคา, จำนวนมาก, ขาย, บริษัท, คลังสินค้า, ค่าใช้จ่าย.
สินค้าที่เกี่ยวข้อง